When the C7000 enclosure was restarted, OA settings were returned to defaults

Unit in Concern
C7000 Blade Enclosure OA





Symptom
When the enclosure was restarted, OA settings were returned to defaults


Description
** Above symptom is due to the failure of the OA internal battery. This is known as "Time Keeper", which is similar to the component installed in the network switches. Without the internal battery, settings of the OA is not saved. 





Action Taken to fix the Issue


* All the settings of the OA was set to defaults
* Password can not be reset by using the script. Even though the script runs, it will not reset the password. 
* In order to reset the password null modem cable and the OA reset switch need to be used

Time Keeper





* OA internal battery was replaced and reconfigure the OA.

Top View of the On board Administrator

OA with top cover removed
( The battery is covered with front collar of the case)

Top view of the OA with circuit board pulled out.
( The battery is visible next to the USB port; right bottom corner)
Battery is located next to the USB port.
(Make sure to plug the battery in correct side: marked ablack circle in an one corner)

** Login password reset method is described in below link